Skip to main content
Siemens 3VA1132-6EF32-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1132-6EF32-0AH0 SENTRON MCCB, 32A, 220kA at 240V

MPN3VA1132-6EF32-0AH0

Siemens SENTRON 3VA1132-6EF32-0AH0, 3-pole molded case circuit breaker, 32 A rated, 220 kA breaking capacity at 240 V AC, line protection design, TM240 overcurrent release.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1132-6EF32-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11326EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1132-6EF32-0AH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C31 A
Current at 60 °C31 A
Current at 65 °C30 A
Current at 70 °C30 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.10.6 W

Protection & Trip Unit

3VA1132-6EF32-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1132-6EF32-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1132-6EF32-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1132-6EF32-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1132-6EF32-0AH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Breaking capacity and selectivity

The 3VA1132-6EF32-0AH0: Breaking capacity drops with voltage: 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 500 V and 690 V. That 17 kA floor at 690 V is the limiting case for coordination studies — if your fault current at the panel exceeds that, you need a higher-rated frame upstream. The TM240 thermal-magnetic release provides fixed thermal and magnetic trip thresholds, suitable for cable and busbar protection where adjustable electronic releases aren't required.

Physical fit and auxiliaries

Dimensions are 130 mm high, 76.2 mm wide, 70 mm deep — a standard 3-pole MCCB footprint that mounts on a DIN rail or panel base. The 70 mm depth is the dimension to check against enclosure gland-plate clearance. Comes with 2 auxiliary switches plus 1 trip alarm switch (HQ) factory-fitted. The basic switch order code is 3VA11326EF320AA0, which is the bare breaker without auxiliaries — this variant includes them pre-assembled.

Thermal derating and operating range

Rated current holds at 32 A from 40 °C through 50 °C, then derates to 31 A at 55–60 °C and 30 A at 65–70 °C. Maximum power loss is 10.6 W. Operating temperature range is -25 °C to +70 °C; storage range is -40 °C to +80 °C.

Frequently asked questions

What is the breaking capacity of 3VA1132-6EF32-0AH0 at different voltages?

220 kA at 240 V AC, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at both 500 V and 690 V. The 690 V figure is the coordination-limiting value.

Where can I buy 3VA1132-6EF32-0AH0 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
3VA1132-6EF32-0AH0