The Siemens SENTRON 3VA1132-6EF32-0JC0 is a 3-pole molded case circuit breaker (MCCB) rated 32 A at 40 °C, with a breaking capacity of 220 kA at 240 V and 154 kA at 415 V.
Breaking capacity and thermal performance
Breaking capacity drops as voltage climbs — 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at both 500 V and 690 V. For a 400 V distribution panel, the 154 kA figure gives you selectivity headroom over downstream breakers. The thermal rating holds at 32 A from 40 °C up to 50 °C, then derates to 31 A at 55–60 °C and 30 A at 65–70 °C — so in a warm enclosure you lose only 2 A worst-case.