Above 50 °C it steps down: 30.72 A at 55 °C, 30.08 A at 60 °C, 29.44 A at 65 °C, and 28.8 A at 70 °C. This MCCB clears 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 690 V. At 415 V the 154 kA figure is high enough for most industrial main or feeder positions without cascading upstream — it lets you coordinate downstream branch breakers with confidence.
The 3VA1132-6EF36-0BC0 mounts in a standard MCCB footprint: 76.2 mm wide, 130 mm high, 70 mm deep. IP40 on the front means it keeps out tools and wires but is not sealed against washdown — install inside a panel enclosure.