SENTRON 3VA1132-6EF36-0CC0 — 32 A MCCB with Undervoltage Release
It carries a 220 kA interrupting capacity at 240 V, dropping to 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 500 V and 690 V. Current rating holds at 32 A from 40 °C through 50 °C ambient, then derates to 31 A at 55–60 °C and 30 A at 65–70 °C. Maximum power loss is 13.1 W.
Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — standard for the SENTRON 3VA frame size.