SENTRON 3VA1132-6EF46-0AA0 — MCCB for line protection
It carries a TM240 thermal-magnetic overcurrent release and is rated for 32 A continuous current at ambient temperatures from 40 °C up to 50 °C, with minor derating to 30 A at 70 °C — useful to know when the breaker sits in a warm panel next to other heat sources. Breaking capacity is 220 kA at 240 V, dropping to 154 kA at 415 V and 121 kA at 440 V.
Dimensions are 101.6 mm wide, 70 mm deep, 130 mm tall — a standard 4-pole MCCB footprint that fits most DIN-rail or panel-mount enclosures without surprises.