Skip to main content
Siemens 3VA1132-6GF46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1132-6GF46-0AA0 MCCB, 70kA @ 415V, 32A, TM240

MPN3VA1132-6GF46-0AA0
Active

Siemens 3VA1132-6GF46-0AA0, IEC 160 A frame molded case circuit breaker, 70 kA breaking capacity at 415 V, 4-pole, TM240 thermal-magnetic trip, In=32 A, Ir=22-32 A, Ii=5-10xIn, line protection, 100 % neutral protection, terminal connection.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Specifications

3VA1132-6GF46-0AA0 — Specifications
ParameterValue
Group codeP360
Product group5375
Product classC: products manufactured / produced to order, which cannot be reused or re-utilized or be returned against credit.
Series3VA Molded Case Circuit Breakers up to 1600 A, IEC
Export control regulationsAL : N / ECCN : N
Compliance with the substance restrictions according to RoHS directiveSince: 01-04-14

Product details

The Siemens 3VA1132-6GF46-0AA0 is a 4-pole IEC molded case circuit breaker on the 160 A frame, rated for a 70 kA breaking capacity at 415 V (breaking capacity class H). The TM240 thermal-magnetic trip unit is set for line protection with an In of 32 A, overload protection adjustable Ir = 22 to 32 A, and short-circuit protection Ii = 5 to 10 x In. That adjustable Ir band lets you fine-tune the overload pickup to match the actual load current on the circuit — useful when the connected load is below the fixed rating. Neutral conductor protection is set at 100 %, meaning the neutral pole is fully protected at the same rating as the phase poles. Terminal connection type suits standard panel wiring.

Lifecycle and compliance — active, RoHS, REACH

RoHS compliance effective from 01-Apr-2014. If you are sourcing for a jurisdiction that requires REACH SVHC declarations, the supplier can provide the duty-to-inform documentation. Product class C (manufactured/produced to order) — this breaker is not a stocked shelf item; it is built to order, which means no returns or reuse. Plan your BOM freeze accordingly.

Frequently asked questions

What is the breaking capacity of this MCCB?

70 kA at 415 V (breaking capacity class H per IEC). That is the maximum fault current it can safely interrupt at that voltage level.

What is the adjustable trip range on this breaker?

Overload protection Ir is adjustable from 22 A to 32 A; short-circuit protection Ii is adjustable from 5 to 10 times In (160 to 320 A at In=32 A).

Where can I buy 3VA1132-6GF46-0AA0 and how is it quoted?

This part is sourced to order against an RFQ through independent distribution. Availability and pricing are confirmed at quote time — it is a build-to-order item, not a stocked shelf good.

What compliance documentation does Siemens provide for this breaker?

RoHS compliance effective 01-Apr-2014. REACH Article 33 disclosure: Lead (CAS 7439-92-1) above 0.1 % w/w. Export control: AL N / ECCN N.

MPN