Skip to main content
Siemens 3VA1140-3ED12-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1140-3ED12-0AA0 SENTRON MCCB, 40A 1-Pole, 52.5kA

MPN3VA1140-3ED12-0AA0
Active

Siemens SENTRON 3VA1140-3ED12-0AA0, 1-pole molded case circuit breaker, 40 A rated current, 52.5 kA breaking capacity at 240 V AC, TM210 overcurrent release, line protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1140-3ED12-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1140-3ED12-0AA0 — Ratings
ParameterValue
Number of poles1
Rated operational voltage Ue (AC)415 V
Rated insulation voltage Ui500 V
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C39 A
Current at 60 °C39 A
Current at 65 °C38 A
Current at 70 °C37 A
Switching capacity classN
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V7.5 kA
Power loss, max.3.6 W
3VA1140-3ED12-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1140-3ED12-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1140-3ED12-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1140-3ED12-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1140-3ED12-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width25.4 mm
Depth70 mm
Height (in)5.12 in
Width (in)1 in
Depth (in)2.76 in

Product details

It carries a TM210 thermal-magnetic overcurrent release, rated 40 A continuous at 40 °C ambient, and breaks up to 52.5 kA at 240 V AC. The 25.4 mm width (1 inch) matches standard DIN-rail or panel-mount footprints — one module wide, so it slots into existing SENTRON sub-distribution boards without re-spacing.

Rated current holds at 40 A through 50 °C, then derates to 39 A at 55–60 °C, and 38 A at 65 °C, 37 A at 70 °C — the TM210 trip curve stays within spec across the operating range. Breaking capacity is 52.5 kA at 240 V AC and 7.5 kA at 415 V AC; the 415 V figure is the one to check if the panel feeds a 400 V line. Insulation voltage is rated 500 V, operating voltage 415 V AC / 125 V DC.

Depth is 70 mm (2.76 in), height 130 mm (5.12 in) — fits standard SENTRON enclosures and most 200 mm-deep distribution boards. Ground-fault monitoring is not built in; if that is needed, add an external module or specify a different variant.

Frequently asked questions

How do I get current pricing and availability for 3VA1140-3ED12-0AA0?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

What is the closest functional second-source to 3VA1140-3ED12-0AA0?

Within the SENTRON family, the 3VA1020-2ED32-0DD0 is a 1-pole MCCB but with a different release and lower breaking capacity — verify your fault level and trip curve before substituting. The 5SJ3140-7 is a miniature circuit breaker (MCB), not a direct MCCB replacement; it occupies the same 1-module width but has a lower interrupting rating.

What compliance documentation does Siemens provide for 3VA1140-3ED12-0AA0?

Standard SENTRON MCCBs carry CE marking, UL/CSA recognition, and RoHS/REACH declarations. Specific certificates are included with the shipment or available on request.

MPN
3VA1140-3ED12-0AA0