What this 40 A MCCB does in the panel
The Siemens 3VA1140-3ED42-0AA0 is a SENTRON 4-pole molded case circuit breaker rated 40 A continuous at 40 °C, with a TM210 thermal-magnetic release for line protection. Four poles let it switch three-phase plus neutral in a single unit, saving DIN rail space over separate breakers.
Breaking capacity across voltages — where it fits
This MCCB delivers 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at both 500 V and 690 V.
Thermal derating — what the 40 A means at panel ambient
At 55 °C it derates to 39 A, at 65 °C to 38 A, and at 70 °C to 37 A. The 10.8 W maximum power loss is modest for a 4-pole 40 A breaker; it won't drive significant internal heating in a ventilated enclosure.
The 101.6 mm width is 4 inches — standard for a 4-pole MCCB footprint on DIN rail or panel-mount.