Siemens 3VA1140-3EF32-0AD0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1140-3EF32-0AD0 SENTRON MCCB, 40 A, 75.6 kA at 24

MPN3VA1140-3EF32-0AD0

Siemens SENTRON 3VA1140-3EF32-0AD0, 3-pole molded case circuit breaker, 40 A rated, TM240 thermal-magnetic release, line protection, 70 mm depth, 76.2 mm width.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1140-3EF32-0AD0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11403EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1140-3EF32-0AD0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C39 A
Current at 60 °C39 A
Current at 65 °C38 A
Current at 70 °C37 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.10.8 W
3VA1140-3EF32-0AD0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1140-3EF32-0AD0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1140-3EF32-0AD0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1140-3EF32-0AD0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1140-3EF32-0AD0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Breaking capacity is the headline here: 75.6 kA at 240 VAC, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at both 500 V and 690 V. Power loss at rated load is 10.8 W — negligible for panel thermal budgeting but worth noting if you're packing breakers tight in a sealed enclosure.

At 55 °C it drops to 39 A, at 65 °C to 38 A, and at 70 °C to 37 A.

Panel fit and auxiliary switch configuration

Comes with three auxiliary switches (HQ type) pre-installed — no separate order for status feedback. If you need shunt trip or remote signaling, you're looking at a different suffix in the 3VA1 family.

Frequently asked questions

Does this breaker include auxiliary contacts or a shunt trip?

It includes three pre-installed HQ-type auxiliary switches. No undervoltage release, no ground-fault monitoring, and no communication module on this variant.

MPN