Its 40 A rated continuous current (Iu) holds flat from 40 °C to 50 °C, then derates to 36 A at 70 °C — so a panel ambient of 55 °C or higher clips the usable load by 1.6 A to 4 A, something a panel builder needs to factor into the fill factor and gland plate layout. Breaking capacity steps with system voltage: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V.
Latching endurance rated at 15,000 operations. The trip indicator gives a local visual flag for fault isolation.