Skip to main content
Siemens 3VA1140-3EF32-0AG0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1140-3EF32-0AG0 SENTRON MCCB, 40A, 3-Pole, 75.6kA

MPN3VA1140-3EF32-0AG0

Siemens SENTRON 3VA1140-3EF32-0AG0, molded case circuit breaker, 3-pole, 40 A rated, TM240 overcurrent release, line protection, 75.6 kA interrupting capacity at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1140-3EF32-0AG0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11403EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB11
3VA1140-3EF32-0AG0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C39 A
Current at 60 °C39 A
Current at 65 °C38 A
Current at 70 °C37 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.10.8 W
3VA1140-3EF32-0AG0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1140-3EF32-0AG0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1140-3EF32-0AG0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1140-3EF32-0AG0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1140-3EF32-0AG0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

MCCB for line protection — 40 A frame, TM240 release

The TM240 overcurrent release is a fixed thermal-magnetic type — no electronic adjustment, no communication function. That makes it a straightforward drop-in for standard feeder or branch protection where you don't need selective coordination tuning. Interrupting capacity is specified per voltage: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at both 500 V and 690 V.

The width is a standard 3-inch (76.2 mm) footprint, so it aligns with common DIN-rail or backplate mounting patterns.

Frequently asked questions

What does the TM240 release designation mean?

TM240 indicates a fixed thermal-magnetic overcurrent release — thermal element for overload protection, magnetic element for short-circuit protection. No electronic adjustment or communication interface.

MPN