Skip to main content
Siemens 3VA1140-3EF32-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1140-3EF32-0AH0 SENTRON MCCB, 40 A, 3-Pole

MPN3VA1140-3EF32-0AH0

Siemens SENTRON 3VA1140-3EF32-0AH0, molded case circuit breaker, 3-pole, 40 A, TM240 thermal-magnetic release, line protection, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1140-3EF32-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1140-3EF32-0AH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C38.4 A
Current at 60 °C37.6 A
Current at 65 °C36.8 A
Current at 70 °C36 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V10.5 kA
3VA1140-3EF32-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1140-3EF32-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1140-3EF32-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1140-3EF32-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1140-3EF32-0AH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Short-circuit breaking capacity is given at four system voltages: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V. That covers the common industrial distribution voltages across North America (240/480 V) and Europe (400/415 V). At 415 V, the 52.5 kA rating gives solid headroom for most panelboards — you can usually achieve selective coordination downstream without oversizing upstream breakers.

Thermal derating — the real-world current limit

Above that it derates linearly: 38.4 A at 55 °C, 37.6 A at 60 °C, 36.8 A at 65 °C, and 36 A at 70 °C.

Physical fit and auxiliary contacts

Dimensions are 130 mm high, 76.2 mm wide, and 70 mm deep — a compact footprint for a 40 A MCCB that fits most DIN-rail or panel-mount arrangements.

MPN
3VA1140-3EF32-0AH0