Line protection MCCB with TM240 release
The interrupting capacity reaches 75.6 kA at 240 V, 52.5 kA at 415 V, and 32 kA at 440 V — numbers that govern the available fault current the breaker can clear without upstream coordination issues.
The 40 A rating holds flat from 40 °C to 50 °C, then derates to 38.4 A at 55 °C and 36 A at 70 °C. The TM240 release provides thermal protection for overloads and magnetic trip for short-circuits; there's no separate ground-fault or voltage-trigger function built in. The interrupting ratings at 240 V (75.6 kA), 415 V (52.5 kA), and 440 V (32 kA) cover most industrial distribution panels.
Integrated undervoltage release and auxiliary contacts
Dimensions are 130 mm high, 76.2 mm wide, and 70 mm deep — fits standard 3-pole MCCB panel cutouts. The breaker is rated for 15 000 mechanical/electrical operations (latching endurance), a solid figure for typical industrial duty.