Skip to main content
Siemens 3VA1140-3EF32-0CC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1140-3EF32-0CC0 SENTRON MCCB, 40 A, 75.6 kA at 24

MPN3VA1140-3EF32-0CC0

Siemens SENTRON 3VA1140-3EF32-0CC0, molded case circuit breaker, 3-pole, 40 A (40 °C), breaking capacity 75.6 kA at 240 V, 52.5 kA at 415 V, undervoltage release, 70 mm depth, 76.2 mm width, 130 mm height.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1140-3EF32-0CC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11403EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1140-3EF32-0CC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C39 A
Current at 60 °C39 A
Current at 65 °C38 A
Current at 70 °C37 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.13.3 W
3VA1140-3EF32-0CC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1140-3EF32-0CC0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1140-3EF32-0CC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1140-3EF32-0CC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1140-3EF32-0CC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Line protection breaker with high interrupting capacity

That thermal stability means it holds its rating across typical panel internal temperatures without oversizing. Breaking capacity is the headline number here: 75.6 kA at 240 V, 52.5 kA at 415 V, and still 32 kA at 440 V. For a 40 A frame, those are high-interrupt ratings — the breaker can clear a bolted fault on a large transformer secondary or a motor-control center bus without upstream fuses. No communication module or ground-fault monitoring is fitted on this variant.

Mounting is via rear DIN rail or screw-mount plate. Maximum power loss is 13.3 W at rated load — negligible for thermal management in a ventilated panel, but worth noting for sealed enclosures where internal temperature rise must be calculated.

Frequently asked questions

Does 3VA1140-3EF32-0CC0 include an undervoltage release?

Yes, it comes with an undervoltage release (UVR) as standard, which trips the breaker when control voltage drops — typical for safety circuits or emergency-stop applications.

MPN
3VA1140-3EF32-0CC0