Its interrupting capacity hits 75.6 kA at 240 V and 52.5 kA at 415 V, so it handles high-fault utility feeds without cascading upstream.
Current derating and thermal reality
Above that, derating begins: 38.4 A at 55 °C, 37.6 A at 60 °C, 36.8 A at 65 °C, and 36 A at 70 °C. Rated insulation voltage is 800 V, and interrupting capacity at 690 V is still 10.5 kA — enough for 690 V industrial grids with moderate fault levels. Mechanical endurance is 15,000 cycles, typical for a distribution-grade MCCB.
Integration and auxiliary contacts
Three auxiliary switches (HQ type) are built in — enough for remote status feedback or interlocking without an add-on module. No trip indicator is fitted, so a remote indication relies on the auxiliary contacts.