It carries a 40 A continuous rating at 40 °C and breaks up to 121 kA at 240 V, 75.6 kA at 415 V, and 52.5 kA at 440 V — the interrupting capacity drops to 11.9 kA at 500 V and 690 V, so verify your fault level at the service voltage.
Three poles, 40 A frame, with a TM220 thermal-magnetic overcurrent release. The 40 A rating holds steady up to 50 °C; at 55 °C it derates to 39 A, and at 70 °C to 37 A — useful if the breaker sits in a warm enclosure near other heat sources.