The interrupting capacity reaches 121 kA at 240 V and 75.6 kA at 415 V, which means it can safely clear high-fault currents on the secondary side of a distribution transformer without upstream fuse coordination failure.
Thermal-magnetic curve and derating across temperature
Above that, derating begins: 38.4 A at 55 °C, 37.6 A at 60 °C, 36.8 A at 65 °C, and 36 A at 70 °C.
Shunt trip and auxiliary contacts for remote control
The auxiliary release order code is 3VA9688-0BL30.
Front IP40 protection means it is suitable for enclosed panels but not for washdown zones.