Skip to main content
Siemens 3VA1140-4EF32-0KH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1140-4EF32-0KH0 SENTRON MCCB, 40 A, 3-Pole, 121 k

MPN3VA1140-4EF32-0KH0

Siemens SENTRON 3VA1140-4EF32-0KH0, molded case circuit breaker, 40 A, 3-pole, 121 kA at 240 V, line protection, with shunt trip and auxiliary switches.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1140-4EF32-0KH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11404EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1140-4EF32-0KH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C39 A
Current at 60 °C39 A
Current at 65 °C38 A
Current at 70 °C37 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.10.8 W
3VA1140-4EF32-0KH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1140-4EF32-0KH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1140-4EF32-0KH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1140-4EF32-0KH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1140-4EF32-0KH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Its interrupting capacity reaches 121 kA at 240 V AC, 75.6 kA at 415 V, and 52.5 kA at 440 V — figures that govern its fault-clearing ability on high-capacity transformers or busway feeds.

At 415 V the breaker clears 75.6 kA; at 500 V and 690 V it still manages 11.9 kA. That spread covers most 400 V-class industrial mains without requiring a current-limiting fuse upstream. The thermal rating holds at 40 A from 40 °C to 50 °C, then tapers to 37 A at 70 °C — the derating curve matters if the breaker sits inside a hot enclosure near other heat sources.

Body measures 130 mm high, 76.2 mm wide, 70 mm deep — a standard 3-pole MCCB footprint for DIN-rail or screw-mount panel integration. The 70 mm depth leaves clearance for rear busbar connections in a typical 200 mm deep enclosure.

A voltage-trip indicator is present; undervoltage release is not fitted. No ground-fault monitoring or communication module is included — it is a plain line-protection breaker with remote-trip capability.

Frequently asked questions

What is the breaking capacity of this MCCB at 240 V?

The interrupting rating is 121 kA at 240 V AC.

Where can I buy 3VA1140-4EF32-0KH0?

This breaker is sourced to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

MPN
3VA1140-4EF32-0KH0