Breaking capacity varies sharply with system voltage: 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V.
Above 50 °C it begins to derate: 39 A at 55 °C and 60 °C, 38 A at 65 °C, 37 A at 70 °C. Physical footprint is 130 mm height, 76.2 mm width, 70 mm depth — a compact 3-pole MCCB that fits standard panel-mount cutouts. Maximum power loss at rated load is 13.3 W; factor that into your enclosure thermal budget, especially in sealed cabinets.
Because it is an active catalog item, the normal Siemens distribution channel carries it. No minimum commitment required for a single-line BOM fill.