Skip to main content
Siemens 3VA1140-4EF36-0JA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1140-4EF36-0JA0 SENTRON MCCB, 40 A, 3-Pole, 121 k

MPN3VA1140-4EF36-0JA0

Siemens SENTRON 3VA1140-4EF36-0JA0, 3-pole molded case circuit breaker, 40 A rated continuous current (Iu), TM240 thermal-magnetic release, line protection version, IP40 front, 70 mm depth.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1140-4EF36-0JA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1140-4EF36-0JA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C38.4 A
Current at 60 °C37.6 A
Current at 65 °C36.8 A
Current at 70 °C36 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA
3VA1140-4EF36-0JA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1140-4EF36-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1140-4EF36-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1140-4EF36-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1140-4EF36-0JA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens 3VA1140-4EF36-0JA0 is a 3-pole molded case circuit breaker from the SENTRON 3VA series, rated for a continuous current Iu of 40 A and an insulation voltage Ui of 800 V. The interrupting ratings are 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V, covering most industrial distribution fault levels. The 40 A rating holds flat from 40 °C through 50 °C, then derates linearly to 36 A at 70 °C — a clean thermal curve that avoids surprises in a warm enclosure. The 70 mm depth and 76.2 mm width fit the standard SENTRON 3VA panel footprint, so a swap from a same-frame 3VA breaker requires no bus-bar rework.

Panel Fit & Integration

The 76.2 mm width (4 module spaces on a 18 mm pitch) and 130 mm height leave clearance for adjacent breakers and bus-bar connections. The IP40 front protection suits enclosed distribution boards; no additional gland-plate sealing is needed for dry indoor locations.

The TM240 release combines a thermal bimetal for overload protection and a magnetic coil for short-circuit protection. The shunt trip (STL) allows remote tripping from a PLC or emergency-stop circuit, using an auxiliary release order code 3VA9688-0BL32. No auxiliary contacts, undervoltage release, or communication function are fitted on this variant — those are separate add-on modules if needed.

Frequently asked questions

Where can I buy 3VA1140-4EF36-0JA0 and what is the lead time?

This part is sourced to order through independent distribution. Submit an RFQ for current availability and lead time — pricing and stock are confirmed at quote time.

What are the interrupting ratings for 3VA1140-4EF36-0JA0?

121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V.

What is the thermal derating curve for this MCCB?

The 40 A rating holds at 40 °C through 50 °C, then derates to 38.4 A at 55 °C, 37.6 A at 60 °C, 36.8 A at 65 °C, and 36 A at 70 °C.

Will 3VA1140-4EF36-0JA0 drop into a panel specified around 3VA1110-5EE32-0JA0?

Both are 3-pole SENTRON 3VA breakers sharing the same 70 mm depth and 76.2 mm width, so the mechanical footprint is identical. The functional difference is the TM240 release and shunt trip on this unit versus the other variant's release — verify the trip curve and accessories match your protection scheme before swapping.

MPN
3VA1140-4EF36-0JA0