Skip to main content
Siemens 3VA1140-5ED26-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1140-5ED26-0AA0 SENTRON MCCB, 40 A, 2-Pole, 187 k

MPN3VA1140-5ED26-0AA0
Active

Siemens SENTRON 3VA1140-5ED26-0AA0, molded case circuit breaker, 2-pole, 40 A continuous rating, 187 kA interrupting at 240 VAC, TM210 thermal-magnetic release, line protection version.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1140-5ED26-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1140-5ED26-0AA0 — Ratings
ParameterValue
Number of poles2
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C39 A
Current at 60 °C39 A
Current at 65 °C38 A
Current at 70 °C37 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Power loss, max.7.2 W

Protection & Trip Unit

3VA1140-5ED26-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout

Construction & Connection

3VA1140-5ED26-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1140-5ED26-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0

Environmental

3VA1140-5ED26-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1140-5ED26-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width50.8 mm
Depth70 mm
Height (in)5.1 in
Width (in)2 in
Depth (in)2.8 in

Product details

40 A MCCB with 187 kA interrupting capacity — what the ratings mean for fit

The Siemens 3VA1140-5ED26-0AA0 is a 2-pole SENTRON molded case circuit breaker rated for 40 A continuous at 40 °C, with a TM210 thermal-magnetic release providing LI protection (long-time and instantaneous). The interrupting capacity is 187 kA at 240 VAC and 121 kA at 415 VAC — these are the maximum fault currents the breaker can safely clear at those voltages without welding or rupturing. The 187 kA figure at 240 V means this breaker is sized for high-fault-capacity service entrance or distribution panels where available fault current exceeds typical 25 kA or 65 kA MCCB ratings. The short-circuit release (Ii) is fixed at 400 A, which is 10× the continuous rating — a standard instantaneous pickup for motor or feeder protection where nuisance tripping on inrush must be avoided.

Mounting dimensions and panel integration

The breaker measures 130 mm high, 50.8 mm wide (2 inches — standard 2-pole MCCB footprint), and 70 mm deep. The 50.8 mm width means it occupies two 25.4 mm pole spaces in a panelboard or switchboard. The IP40 rating on the front face indicates protection against tools and wires greater than 1 mm, but not against water ingress — suitable for indoor panel mounting where the enclosure provides the environmental seal. The 70 mm depth is the body depth; account for handle throw and rear terminal clearance when laying out the gland plate or back panel.

Thermal derating and operating limits

The breaker holds its full 40 A rating from 40 °C through 50 °C. At 55 °C it derates to 39 A, at 65 °C to 38 A, and at 70 °C to 37 A. The maximum operating ambient is 70 °C; storage range is -40 °C to 80 °C. For a panel running warm — say 55 °C inside the enclosure — the continuous load should not exceed 39 A per pole. The power loss at rated current is 7.2 W maximum, which is low enough that forced ventilation is not required in a typical panel, but worth summing across multiple breakers in a sealed enclosure.

DC rating and application notes

The maximum rated operational voltage for DC applications is 250 V. The overcurrent release is the TM210 thermal-magnetic type with LI protection — thermal for overload, magnetic for short circuit. The breaker does not include ground-fault monitoring, communication functions, or a motor drive option. For DC switching power values, Siemens directs to the 3VA molded case circuit breaker device manual for specific derating curves.

Frequently asked questions

What is the interrupting capacity of 3VA1140-5ED26-0AA0 at 240 V and 415 V?

At 240 VAC the interrupting capacity is 187 kA; at 415 VAC it is 121 kA. These are the maximum fault currents the breaker can safely clear at those voltages.

What are the mounting dimensions of 3VA1140-5ED26-0AA0?

Height is 130 mm, width is 50.8 mm (2 inches, standard 2-pole MCCB footprint), and depth is 70 mm.

Where can I buy 3VA1140-5ED26-0AA0 and how is it quoted?

This part is sourced and quoted to order through independent distribution. Availability and current pricing are confirmed at quote time against an RFQ — no stock count or price is published here.

What compliance documentation does Siemens provide for 3VA1140-5ED26-0AA0?

As a SENTRON 3VA series MCCB, the 3VA1140-5ED26-0AA0 carries CE marking for the European market and is designed to meet IEC 60947-2. The manufacturer provides a declaration of conformity and the product manual with specific DC derating curves per the device manual referenced in the specification.

MPN
3VA1140-5ED26-0AA0