The interrupting capacity at 240 V AC is 187 kA, dropping to 121 kA at 415 V AC, 75.6 kA at 440 V AC, and 17 kA at 690 V AC. These ratings are for AC networks; for DC applications, consult the 3VA device manual.
Above that, the continuous current drops linearly: 38.4 A at 55 °C, 37.6 A at 60 °C, 36.8 A at 65 °C, and 36 A at 70 °C. Front IP40 protection means it is suitable for general indoor panel environments but not washdown areas. Dimensions are 76.2 mm wide, 130 mm high, 70 mm deep — a standard 3-pole MCCB footprint for DIN-rail or screw-mount panel integration.
The 3VA1140-5EF36-0AB0 is a current-production Siemens SENTRON MCCB.