Skip to main content
Siemens 3VA1140-5EF36-0DH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1140-5EF36-0DH0 SENTRON MCCB, 40 A, 3-Pole, 187 k

MPN3VA1140-5EF36-0DH0

Siemens SENTRON 3VA1140-5EF36-0DH0, molded case circuit breaker, 3-pole, 40 A, line protection, interrupting 187 kA at 240 V, 121 kA at 415 V, with undervoltage release.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1140-5EF36-0DH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11405EF360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1140-5EF36-0DH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C39 A
Current at 60 °C39 A
Current at 65 °C38 A
Current at 70 °C37 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.13.3 W
3VA1140-5EF36-0DH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1140-5EF36-0DH0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1140-5EF36-0DH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1140-5EF36-0DH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1140-5EF36-0DH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

It holds 40 A continuous at 40 °C through 50 °C without derating, then steps down to 39 A at 55 °C and 60 °C, 38 A at 65 °C, and 37 A at 70 °C — so the 40 A frame stays usable across a typical 50 °C panel ambient without bumping frame size. Interrupting capacity is the headline: 187 kA at 240 VAC, 121 kA at 415 VAC, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V.

Integration and auxiliary fit

No ground-fault monitoring module is fitted; this is a straight line-protection MCCB. No communication function — it's a hard-wired breaker, not a metering or IoT device. Dimensions: 70 mm deep, 76.2 mm wide, 130 mm tall (–) — standard 3-pole MCCB footprint for DIN-rail or panel-mount backplate integration.

Environmental and compliance range

The storage minimum matters for cold warehouse or unheated site storage before commissioning — the breaker can sit at -40 °C without damage, though it must be at operating temperature before being loaded.

Frequently asked questions

How do I get current pricing and availability for 3VA1140-5EF36-0DH0?

Submit an RFQ against this order code. Pricing and availability are confirmed at quote time through independent distribution channels.

What is the interrupting capacity of 3VA1140-5EF36-0DH0 at 240 V?

187 kA at 240 VAC, which qualifies it for high-fault service-entrance applications. At 415 V it is 121 kA, at 440 V it is 75.6 kA, and at 500 V and 690 V it holds 17 kA (–).

What is the rated current of 3VA1140-5EF36-0DH0 and how does it derate with temperature?

Rated 40 A continuous from 40 °C to 50 °C (–). It derates to 39 A at 55 °C and 60 °C (–), 38 A at 65 °C, and 37 A at 70 °C. No derating needed up to 50 °C ambient.

MPN