Siemens 3VA1140-5GD42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1140-5GD42-0AA0 SENTRON MCCB, 40 A, 4-Pole, 187 k

MPN3VA1140-5GD42-0AA0
Active

Siemens SENTRON 3VA1140-5GD42-0AA0, molded case circuit breaker, 4-pole, 40 A, TM210 thermal-magnetic release, line protection, breaking capacity 187 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1140-5GD42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA1140-5GD42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C39 A
Current at 60 °C39 A
Current at 65 °C38 A
Current at 70 °C37 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.10.8 W

Protection & Trip Unit

3VA1140-5GD42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1140-5GD42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1140-5GD42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1140-5GD42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1140-5GD42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

Rated current, breaking capacity, and what they mean for the panel

The 3VA1140-5GD42-0AA0 is a Siemens SENTRON molded case circuit breaker (MCCB) rated for a continuous 40 A on all four poles, designed for line protection in distribution panels. That 40 A holds flat from 40 °C up to 50 °C — only above 55 °C does it begin to derate, dropping to 39 A at 55 °C and 37 A at 70 °C, so in a warm enclosure you still have nearly full rated capacity. The breaking capacity is where this breaker earns its place: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 500 V and 690 V. Those figures mean it can safely interrupt a fault of that magnitude without welding contacts or cascading failure upstream — critical for high-fault installations like transformer secondaries or large motor control centers.

TM210 release and thermal-magnetic trip curve

The overcurrent release is designated TM210, a thermal-magnetic type that provides inverse-time overload protection via a bimetal element and instantaneous short-circuit protection via a solenoid. This is the standard choice for general distribution and feeder circuits where you need coordination downstream without nuisance tripping on motor inrush. The rated insulation voltage is 800 V, so the breaker is suitable for 690 V systems with margin. Power loss at rated current is 10.8 W — a figure worth noting for thermal calculations inside a sealed enclosure.

Lifecycle and sourcing — active, no obsolescence concern

This part carries a lifecycle status of current production. There is no end-of-life notice, no last-time-buy window, and no successor part number to track. For the BOM freeze or the MRO planner stocking a spares cabinet, that means the supply channel is stable — no urgency to buy ahead of a phase-out. Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

Dimensions and panel fit

The breaker measures 70 mm deep, 101.6 mm wide, and 130 mm high. The 4-pole width of roughly 100 mm is the standard 4-module footprint for SENTRON 3VA breakers; it mounts on a DIN rail or directly to a mounting plate via screw terminals. Front protection is IP40, meaning tools and fingers are kept out but the device is not sealed against moisture — install inside a rated enclosure. No undervoltage release, no communication function, no ground-fault monitoring on this variant; it is a straight thermal-magnetic line-protection device.

Frequently asked questions

Where can I buy 3VA1140-5GD42-0AA0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent industrial distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the breaking capacity of this MCCB at 415 V?

At 415 V the breaking capacity is 121 kA. At 240 V it is 187 kA, at 440 V it is 75.6 kA, and at 500 V and 690 V it is 17 kA.

Does the 3VA1140-5GD42-0AA0 include an undervoltage release or communication?

No. This variant has no undervoltage release, no communication function, and no ground-fault monitoring. It is a straight thermal-magnetic line-protection breaker with a TM210 release.

MPN