Skip to main content
Siemens 3VA1140-6ED42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1140-6ED42-0AA0 SENTRON MCCB, 40 A, 4-Pole, 220 k

MPN3VA1140-6ED42-0AA0
Active

Siemens SENTRON 3VA1140-6ED42-0AA0, molded case circuit breaker, 4-pole, 40 A (40 °C), TM210 release, 220 kA at 240 V, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1140-6ED42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA1140-6ED42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C39 A
Current at 60 °C39 A
Current at 65 °C38 A
Current at 70 °C37 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.10.8 W

Protection & Trip Unit

3VA1140-6ED42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1140-6ED42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1140-6ED42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1140-6ED42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1140-6ED42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

Siemens SENTRON 3VA1140-6ED42-0AA0 — 40 A MCCB with TM210 Release

The Siemens SENTRON 3VA1140-6ED42-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated for line protection, carrying 40 A continuously at 40 °C ambient without derating. The TM210 thermal-magnetic release handles overloads and short-circuits in one compact package — no separate trip unit to order. Breaking capacity hits 220 kA at 240 V AC, which is enough for high-fault utility feeds or transformer secondaries where the available fault current is substantial. The 800 V rated insulation voltage gives headroom for 480 V and 600 V class systems without creeping along the edge of the rating.

Thermal Derating and Panel Integration

The 40 A rating holds flat from 40 °C through 50 °C, then drops to 39 A at 55–60 °C and 38 A at 65 °C, reaching 37 A at 70 °C. That is a shallow derating curve — only 3 A lost across a 30 °C rise — so it handles warm enclosures without oversizing the frame. The 70 mm depth and 101.6 mm width fit standard Siemens 3VA panel footprints; the IP40 front protection means it is suitable for enclosed distribution boards where the front face is behind a door. Maximum power loss is 10.8 W, which factors into enclosure thermal calculations when grouping several breakers.

Frequently asked questions

What is the breaking capacity of this MCCB at different voltages?

At 240 V it interrupts 220 kA, at 415 V it is 154 kA, at 440 V it is 121 kA, and at 500 V and 690 V it is 17 kA.

What is the rated current at elevated ambient temperatures?

It carries 40 A from 40 °C to 50 °C, then derates to 39 A at 55–60 °C, 38 A at 65 °C, and 37 A at 70 °C.

Where can I buy 3VA1140-6ED42-0AA0 and what is the lead time?

This part is sourced and quoted to order against an RFQ through our independent distribution network. Current pricing and lead time are confirmed at the time of quotation.

What type of overcurrent release does this breaker use?

It uses a TM210 thermal-magnetic fixed release — no separate trip unit required.

MPN
3VA1140-6ED42-0AA0