Skip to main content
Siemens 3VA1140-6EE32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1140-6EE32-0AA0 SENTRON MCCB, 40 A, 220 kA at 240

MPN3VA1140-6EE32-0AA0
Active

Siemens SENTRON 3VA1140-6EE32-0AA0, molded case circuit breaker, 3-pole, 40 A at 40 °C, TM220 overcurrent release, 220 kA interrupting at 240 V, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1140-6EE32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA1140-6EE32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C39 A
Current at 60 °C39 A
Current at 65 °C38 A
Current at 70 °C37 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.10.8 W

Protection & Trip Unit

3VA1140-6EE32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1140-6EE32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1140-6EE32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1140-6EE32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1140-6EE32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

What this MCCB delivers

The Siemens 3VA1140-6EE32-0AA0 is a SENTRON molded case circuit breaker (MCCB) rated 40 A at 40 °C, with a TM220 thermal-magnetic overcurrent release. It is designed for line protection in distribution panels. The interrupting rating hits 220 kA at 240 V, 154 kA at 415 V, and 121 kA at 440 V — enough for high-fault industrial services. Insulation voltage is rated 800 V, so this breaker handles 480/600 V class systems without derating the insulation.

Panel fit and mounting

The 3VA1140-6EE32-0AA0 occupies a 76.2 mm wide, 130 mm tall, 70 mm deep footprint — standard for a 3-pole SENTRON 3VA1 frame. Mounts on DIN rail or direct panel. Front face carries IP40 protection, so it's fine inside a clean enclosure but not for washdown areas. The TM220 release is fixed; no trip indicator or undervoltage release on this variant.

Thermal derating and real-world current

Rated 40 A from 40 °C up to 50 °C; at 55 °C it drops to 39 A, at 65 °C to 38 A, and at 70 °C to 37 A. That's a shallow derating curve — good for warm panels. Maximum power loss is 10.8 W, so heat buildup in a dense cabinet is manageable. Operating temperature range is -25 °C to 70 °C.

Frequently asked questions

Where can I buy 3VA1140-6EE32-0AA0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the interrupting rating of 3VA1140-6EE32-0AA0 at 240 V?

The interrupting rating is 220 kA at 240 V. It also carries 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 500 V and 690 V.

Does 3VA1140-6EE32-0AA0 have a trip indicator or undervoltage release?

No. This variant has no trip indicator and no undervoltage release.

MPN
3VA1140-6EE32-0AA0