Skip to main content
Siemens 3VA1140-6EF32-0CA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1140-6EF32-0CA0 SENTRON MCCB, 40 A, 3-Pole, 220 k

MPN3VA1140-6EF32-0CA0

Siemens SENTRON 3VA1140-6EF32-0CA0, molded case circuit breaker, 3-pole, 40 A rated at 40 °C, 220 kA breaking capacity at 240 V, line protection design with undervoltage release.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1140-6EF32-0CA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11406EF320AA0
3VA1140-6EF32-0CA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C39 A
Current at 60 °C39 A
Current at 65 °C38 A
Current at 70 °C37 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.13.3 W
3VA1140-6EF32-0CA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1140-6EF32-0CA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1140-6EF32-0CA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1140-6EF32-0CA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1140-6EF32-0CA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1140-6EF32-0CA0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current of 40 A at 40 °C ambient and derating to 37 A at 70 °C. It is designed for main feeder or large branch-circuit protection in industrial panels, switchboards, and motor control centers.

Breaking capacity — what the voltage columns mean

This MCCB delivers 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and holds 17 kA at both 500 V and 690 V.

Built-in undervoltage release

The UVR automatically trips the breaker when supply voltage drops below a threshold — common on safety circuits, emergency-stop chains, or any load that must not auto-restart after a brownout. No communication function or ground-fault monitoring is fitted on this variant.

The 3-pole footprint matches standard SENTRON 3VA mounting patterns — it installs on a DIN rail or bolts directly into a panel bus. The 70 mm depth keeps it within typical enclosure clearances for distribution boards and motor control centers.

Frequently asked questions

Where can I buy 3VA1140-6EF32-0CA0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ to confirm current availability and pricing at quote time.

What is 3VA1140-6EF32-0CA0's listed depth?

The listed depth is 70 mm (2.76 in).

What compliance documentation does this brand provide for 3VA1140-6EF32-0CA0?

As a Siemens SENTRON MCCB, it carries the standard industrial approvals expected for this class — UL, CSA, IEC, and CE. Specific RoHS and REACH declarations are available from Siemens documentation.

MPN
3VA1140-6EF32-0CA0