Siemens 3VA1140-6EF36-0BC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1140-6EF36-0BC0 SENTRON MCCB, 40A, 3P, 220kA @240

MPN3VA1140-6EF36-0BC0

Siemens SENTRON 3VA1140-6EF36-0BC0, molded case circuit breaker, 3-pole, 40 A rated at 40 °C, breaking capacity 220 kA at 240 V, line protection design, with undervoltage release.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1140-6EF36-0BC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11406EF360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1140-6EF36-0BC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C39 A
Current at 60 °C39 A
Current at 65 °C38 A
Current at 70 °C37 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.13.3 W
3VA1140-6EF36-0BC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1140-6EF36-0BC0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1140-6EF36-0BC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1140-6EF36-0BC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1140-6EF36-0BC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Its interrupting capacity reaches 220 kA at 240 V, 154 kA at 415 V, and 121 kA at 440 V — figures that place it in the high-breaking class for industrial feeder and distribution panels.

Ratings and thermal behaviour

The 40 A rating holds steady from 40 °C to 50 °C, then derates to 39 A at 55 °C and 60 °C, 38 A at 65 °C, and 37 A at 70 °C. That means in a warm panel — say 55 °C ambient — the breaker still handles 39 A continuous without nuisance tripping.

Dimensions are 130 mm high, 76.2 mm wide, 70 mm deep — fits standard 3-pole MCCB panel cutouts. The supplied basic switch is 3VA11406EF360AA0.

Frequently asked questions

Where can I buy 3VA1140-6EF36-0BC0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of this MCCB at 415 V?

At 415 V the breaking capacity is 154 kA.

Does 3VA1140-6EF36-0BC0 include an undervoltage release?

Yes, it includes an undervoltage release (UVR) as the auxiliary release type, plus two auxiliary switches (HQ design).

MPN