Skip to main content
Siemens 3VA1140-6GE46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1140-6GE46-0AA0 SENTRON MCCB, 40 A, 4-Pole, 220 k

MPN3VA1140-6GE46-0AA0
Active

Siemens SENTRON 3VA1140-6GE46-0AA0, molded case circuit breaker, 4-pole, 40 A fixed rating, TM220 release, breaking capacity 220 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1140-6GE46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA1140-6GE46-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C39 A
Current at 60 °C39 A
Current at 65 °C38 A
Current at 70 °C37 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.10.8 W

Protection & Trip Unit

3VA1140-6GE46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1140-6GE46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1140-6GE46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1140-6GE46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1140-6GE46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

Fixed 40 A, 4-pole MCCB with TM220 release

The Siemens SENTRON 3VA1140-6GE46-0AA0 is a 4-pole molded case circuit breaker with a fixed 40 A rating and a TM220 thermal-magnetic overcurrent release. The TM220 designation means the thermal element is fixed at 40 A (no adjustment range), and the magnetic short-circuit pickup is fixed at 20× the rated current — 800 A. This is a line-protection design, not a motor-protection or adjustable version, so it's suited for feeder circuits where the load current is known and stable. Breaking capacity varies sharply with system voltage: 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at both 500 V and 690 V. At 690 V the 17 kA figure is the limiting factor — verify your available fault current at that voltage before specifying. The insulation voltage is rated 800 V, so the breaker itself is built for 690 V systems, but the interrupting rating drops off above 440 V.

Thermal derating and panel fit

The 40 A rating holds from 40 °C through 50 °C ambient. At 55 °C it derates to 39 A, at 65 °C to 38 A, and at 70 °C to 37 A. In a sealed enclosure or a high-temp panel, use the 70 °C column: 37 A continuous is the real limit. Power loss at full load is 10.8 W maximum — negligible for most enclosures but worth summing if you pack several breakers in a small box. Dimensions: 130 mm height, 101.6 mm width, 70 mm depth. The 70 mm depth is shallow enough for most 200 mm deep enclosures with room for wiring gutters. Width at 101.6 mm (4 inches) is standard for a 4-pole frame — it occupies four 25 mm module positions on a DIN rail, though this is a bolt-on or screw-mount MCCB, not a snap-on MCB. Verify the mounting pattern against your backplate.

Lifecycle and sourcing

The front face carries IP40 protection — suitable for dry indoor panels, not washdown or outdoor use. Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C. No undervoltage release, no communication function, no ground-fault monitoring on this variant — it's a straight thermal-magnetic line-protection breaker.

Frequently asked questions

Where can I buy 3VA1140-6GE46-0AA0 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

What is the breaking capacity of 3VA1140-6GE46-0AA0 at 415 V?

154 kA at 415 V. At 240 V it is 220 kA, at 440 V it is 121 kA, and at 500 V or 690 V it drops to 17 kA.

Will 3VA1140-6GE46-0AA0 drop into a panel specified for 3VA1020-2ED32-0DD0?

The 3VA1020-2ED32-0DD0 is a different frame size and rating — verify mounting pattern and bus bar spacing before substitution. The 3VA1140-6GE46-0AA0 is a 4-pole 40 A fixed breaker; the 3VA1020 is a 2-pole or 3-pole variant with different dimensions. Panel fit is not guaranteed without checking the backplate layout.

MPN
3VA1140-6GE46-0AA0