Skip to main content
Siemens 3VA1150-3EE32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1150-3EE32-0AA0 SENTRON MCCB, 50 A, 75.6 kA

MPN3VA1150-3EE32-0AA0
Active

Siemens SENTRON 3VA1150-3EE32-0AA0, 3-pole molded case circuit breaker, 50 A rated current, 75.6 kA breaking capacity at 240 V, TM220 overcurrent release, line protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1150-3EE32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1150-3EE32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C49 A
Current at 60 °C48 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.14.6 W
3VA1150-3EE32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1150-3EE32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1150-3EE32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1150-3EE32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1150-3EE32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens 3VA1150-3EE32-0AA0 is a SENTRON 3-pole molded case circuit breaker (MCCB) rated for 50 A continuous at 40 °C, with a TM220 thermal-magnetic overcurrent release. Breaking capacity is the headline spec here: 75.6 kA at 240 V AC, 52.5 kA at 415 V, 32 kA at 440 V, and still 11.9 kA at 690 V. That's a high-interrupting rating for a 50 A frame — it clears severe fault currents without upstream fuses needing to blow, which matters for selectivity in a multi-level distribution board. Front face carries IP40 protection.

Above that it drops: 49 A at 55 °C, 48 A at 60 °C, 46 A at 65 °C, 45 A at 70 °C. Maximum power loss is 14.6 W. In a dense panel with multiple breakers side by side, that heat adds up — account for it in the thermal budget, especially if the breaker is enclosed in a gland plate or dead-front. Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — a standard 3-pole MCCB footprint for a 50 A frame.

Frequently asked questions

What overcurrent release does this breaker use?

A TM220 thermal-magnetic release. The thermal element protects against overloads; the magnetic element trips instantaneously on short-circuit. It's fixed, not adjustable — line protection only, not suitable for motor starting duty where adjustable curves are needed.

MPN
3VA1150-3EE32-0AA0