Skip to main content
Siemens 3VA1150-3EE46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1150-3EE46-0AA0 SENTRON MCCB, 50 A, 4-Pole, TM220

MPN3VA1150-3EE46-0AA0
Active

Siemens SENTRON 3VA1150-3EE46-0AA0, molded case circuit breaker, 4-pole, 50 A at 40 °C, TM220 thermal-magnetic release, interrupting rating 75.6 kA at 240 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1150-3EE46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1150-3EE46-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C49 A
Current at 60 °C48 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.14.6 W
3VA1150-3EE46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA1150-3EE46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1150-3EE46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1150-3EE46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1150-3EE46-0AA0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

SENTRON 3VA1150-3EE46-0AA0 — 50 A, 4-Pole MCCB with TM220 Release

The Siemens 3VA1150-3EE46-0AA0 is a SENTRON molded case circuit breaker (MCCB) rated for 50 A continuous at 40 °C, with a 4-pole configuration and a TM220 thermal-magnetic overcurrent release. Its interrupting capacity reaches 75.6 kA at 240 V AC, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at 500 V and 690 V — figures that define its fault-clearing capability at the point of installation. The TM220 release combines a thermal element for overload protection and a magnetic element for short-circuit protection, tuned to the 50 A frame.

Continuous current holds at 50 A from 40 °C through 50 °C, then derates to 49 A at 55 °C, 48 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C — the thermal curve governs panel loading when ambient exceeds 50 °C. Maximum power loss is 14.6 W; account for this in enclosure thermal calculations, especially in sealed cabinets with multiple breakers.

Dimensions are 130 mm height, 101.6 mm width, and 70 mm depth — the 4-pole width is wider than a 3-pole equivalent, so verify the DIN-rail or mounting-plate allocation before panel layout.

Frequently asked questions

What does the TM220 release designation mean?

TM220 indicates a thermal-magnetic overcurrent release — the thermal element handles overloads, and the magnetic element handles short circuits, both factory-set to the 50 A rating.

MPN
3VA1150-3EE46-0AA0