Skip to main content
Siemens 3VA1150-3EF32-0AF0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1150-3EF32-0AF0 SENTRON MCCB, 50 A, 75.6 kA at 24

MPN3VA1150-3EF32-0AF0

Siemens SENTRON 3VA1150-3EF32-0AF0, molded case circuit breaker, 3-pole, line protection, TM240 overcurrent release, 50 A rated continuous current, 75.6 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1150-3EF32-0AF0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1150-3EF32-0AF0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C48 A
Current at 60 °C47 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V10.5 kA
3VA1150-3EF32-0AF0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1150-3EF32-0AF0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1150-3EF32-0AF0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1150-3EF32-0AF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1150-3EF32-0AF0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The TM240 thermal-magnetic overcurrent release is fixed — no field-swap of the trip unit. Breaking capacity runs 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V; that 75.6 kA figure at 240 V gives headroom for high-fault utility feeds or transformer secondaries where the available fault current is stiff. IP40 on the front means the breaker face is protected against tools and small wires, but the panel enclosure handles the rest.

At 55 °C it steps to 48 A, at 60 °C to 47 A, at 65 °C to 46 A, and at 70 °C to 45 A. The TM240 release is non-adjustable on the time curve (tr min. and tr max. both 1 s), so coordination with downstream devices relies on the fixed thermal band, not a dial.

The 76.2 mm width is a standard 3-pole MCCB footprint — it occupies three 25.4 mm module positions on a DIN rail or panel-mount plate.

Frequently asked questions

Where can I buy 3VA1150-3EF32-0AF0 and what is the lead time?

The breaker is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here.

What is the breaking capacity of 3VA1150-3EF32-0AF0 at different voltages?

75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V. The 240 V figure is the highest and governs high-fault applications like transformer secondaries.

Does 3VA1150-3EF32-0AF0 include auxiliary contacts?

Yes, it ships with 1 auxiliary switch plus 1 trip alarm switch (HQ type) factory-fitted — no separate accessory order needed for basic status signaling.

What is the thermal derating curve for this MCCB?

50 A from 40 °C to 50 °C, then 48 A at 55 °C, 47 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C. Use the 45 A floor for sealed enclosures with no forced cooling.

MPN
3VA1150-3EF32-0AF0