Skip to main content
Siemens 3VA1150-3EF32-0CA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA1150-3EF32-0CA0 MCCB, 50 A, 3-Pole, 75.6

MPN3VA1150-3EF32-0CA0

Siemens SENTRON 3VA series, molded case circuit breaker (MCCB), order code 3VA1150-3EF32-0CA0, 3-pole, 50 A at 40 °C, 75.6 kA breaking capacity at 240 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1150-3EF32-0CA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11503EF320AA0
3VA1150-3EF32-0CA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C49 A
Current at 60 °C48 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.17.1 W
3VA1150-3EF32-0CA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1150-3EF32-0CA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1150-3EF32-0CA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1150-3EF32-0CA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1150-3EF32-0CA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1150-3EF32-0CA0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current of 50 A across the 40 °C to 50 °C ambient range before it begins to derate. Breaking capacity hits 75.6 kA at 240 V AC, 52.5 kA at 415 V, 32 kA at 440 V, and holds 11.9 kA at both 500 V and 690 V — giving you the SCCR headroom for high-fault utility feeds or transformer-secondaries in industrial distribution.

Mounts on a DIN rail or direct panel; the 76.2 mm width (3 in) and 70 mm depth (2.76 in) fit standard SENTRON 3VA cutouts — no gland-plate rework when swapping from an earlier 3VA frame. Maximum power loss of 17.1 W at rated load — factor that into enclosure thermal rise calculations, especially in a sealed panel with other heat sources. Operating range from -25 °C to 70 °C, storage from -40 °C to 80 °C; the derating curve above 50 °C (49 A at 55 °C, 48 A at 60 °C, 46 A at 65 °C, 45 A at 70 °C) is the number to use for high-ambient installations like pump houses or rooftop MCCs.

Frequently asked questions

Will this drop into a panel specified for 3VA1110-5EF32-0LA0 without rewiring?

Both are 3-pole SENTRON 3VA frame MCCBs with the same 76.2 mm width and 70 mm depth, so the physical footprint and DIN-rail mount are identical — no panel rework needed. Verify the continuous current rating difference (50 A vs the peer's rating) against your load.

MPN
3VA1150-3EF32-0CA0