Skip to main content
Siemens 3VA1150-3EF32-0DH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1150-3EF32-0DH0 SENTRON MCCB, 50A, 3-Pole, 75.6kA

MPN3VA1150-3EF32-0DH0

Siemens SENTRON 3VA1150-3EF32-0DH0, molded case circuit breaker (MCCB), 3-pole, 50 A rated current, line protection design, with undervoltage release and auxiliary switch configuration, breaking capacity 75.6 kA at 240 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1150-3EF32-0DH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11503EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1150-3EF32-0DH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C49 A
Current at 60 °C48 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.17.1 W
3VA1150-3EF32-0DH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1150-3EF32-0DH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1150-3EF32-0DH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1150-3EF32-0DH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1150-3EF32-0DH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens 3VA1150-3EF32-0DH0 is a SENTRON molded case circuit breaker (MCCB) rated for 50 A continuous current across a 40 °C to 50 °C ambient — it holds 50 A flat through that range, then derates to 45 A at 70 °C. Three poles, line-protection design, no communication module onboard. The interrupting ratings climb with voltage: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at 500 V and 690 V.

The 3-pole body and integrated UVR mean the breaker occupies the same slot as a base MCCB plus an external undervoltage module — saves one DIN position. Auxiliary switches and trip alarm are pre-wired to the terminal block; no additional wiring for status indication.

Frequently asked questions

What is the breaking capacity of 3VA1150-3EF32-0DH0 at 240 V?

75.6 kA at 240 V AC. At 415 V it is 52.5 kA, at 440 V it is 32 kA, and at 500 V and 690 V it is 11.9 kA.

Does 3VA1150-3EF32-0DH0 include an undervoltage release?

Yes, it is fitted with an undervoltage release (UVR) as standard, plus two auxiliary switches and one trip alarm switch (HQ configuration).

Where can I buy 3VA1150-3EF32-0DH0 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or price is published here.

MPN
3VA1150-3EF32-0DH0