Skip to main content
Siemens 3VA1150-3EF32-0JA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1150-3EF32-0JA0 SENTRON MCCB, 50 A, 3-Pole, 75.6

MPN3VA1150-3EF32-0JA0

Siemens SENTRON 3VA1 molded case circuit breaker, 3VA1150-3EF32-0JA0, 50 A rated continuous current, 3-pole, line protection, TM240 thermal-magnetic release, shunt trip, IP40 front, 75.6 kA interrupting at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1150-3EF32-0JA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1150-3EF32-0JA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C48 A
Current at 60 °C47 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V10.5 kA

Protection & Trip Unit

3VA1150-3EF32-0JA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1150-3EF32-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1150-3EF32-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1150-3EF32-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1150-3EF32-0JA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Siemens 3VA1150-3EF32-0JA0 — 50 A MCCB with Shunt Trip, Line Protection

The Siemens 3VA1150-3EF32-0JA0 is a SENTRON 3VA1 molded case circuit breaker rated for 50 A continuous current (Iu) at 40 °C, with a 3-pole configuration and a TM240 thermal-magnetic overcurrent release. It carries a shunt trip (STL) auxiliary release, making it suited for remote-trip applications in distribution panels or motor control centers where emergency-off or undervoltage-coordination is required. The interrupting ratings are 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V — covering most low-voltage fault-current scenarios across North American and IEC installations. The 3-pole frame with line-protection firmware (no ground-fault, no communication) keeps it a straightforward, high-SCCR choice for feeder or branch-circuit duty. Rated insulation voltage is 800 V, and the breaker is rated for 15,000 latching endurance cycles. Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C. Front protection is IP40, so it's suitable for enclosed panel mounting — not washdown environments.

Sourcing & Lifecycle

The part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time. For a critical-spare holding or a BOM freeze, this is a stable line item — no imminent PCN or LTB to track.

Integration & Mounting

The 3VA1150-3EF32-0JA0 measures 130 mm high, 76.2 mm wide, and 70 mm deep. It mounts on a DIN rail or panel-mount via the SENTRON 3VA1 base. The 3-pole footprint fits standard distribution board cutouts; verify the shunt trip wiring (3VA9688-0BL32 integrated auxiliary trip) before energizing — polarity on the STL coil matters. No auxiliary contact version is fitted, and there is no communication function or phase-failure detection — this is a pure line-protection breaker with a remote-trip shunt. The TM240 release is factory-set; field adjustment is via the front dial if the variant supports it (check the specific 3VA1 manual for the TM240 adjustment range).

Frequently asked questions

What is the interrupting rating of 3VA1150-3EF32-0JA0 at 415 V?

The interrupting rating at 415 V is 52.5 kA. At 240 V it is 75.6 kA, at 440 V it is 32 kA, and at 690 V it is 10.5 kA.

Does the 3VA1150-3EF32-0JA0 include a shunt trip?

Yes, it is equipped with a shunt trip (STL) auxiliary release (design of the auxiliary release: shunt trip). The integrated auxiliary trip part is 3VA9688-0BL32.

Where can I buy the 3VA1150-3EF32-0JA0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

MPN
3VA1150-3EF32-0JA0