Skip to main content
Siemens 3VA1150-3EF32-0JC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1150-3EF32-0JC0 SENTRON MCCB, 50 A, 3-Pole, 75.6

MPN3VA1150-3EF32-0JC0

Siemens SENTRON 3VA1150-3EF32-0JC0, molded case circuit breaker (MCCB), 3-pole, 50 A rated continuous current Iu, 75.6 kA interrupting at 240 V, TM240 thermal-magnetic release, shunt trip STL.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1150-3EF32-0JC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1150-3EF32-0JC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C48 A
Current at 60 °C47 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V10.5 kA
3VA1150-3EF32-0JC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1150-3EF32-0JC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1150-3EF32-0JC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1150-3EF32-0JC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1150-3EF32-0JC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Its interrupting capacity scales with system voltage: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V — so at 415 V it handles bolted faults up to 52.5 kA without upstream fuses, which is the number that decides whether this breaker clears a fault before the transformer secondary trips.

Thermal derating curve — the real current rating at your cabinet temperature

Above that it derates: 48 A at 55 °C, 47 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C. If your panel ambient runs at 55 °C, the breaker's effective continuous current is 48 A — not the nameplate 50 A.

Integration and auxiliaries

Dimensions: 130 mm height, 76.2 mm width (standard 3-pole MCCB footprint), 70 mm depth.

Frequently asked questions

How do I get current pricing and availability for 3VA1150-3EF32-0JC0?

Submit an RFQ through this listing. The part is sourced to order; availability and current pricing are confirmed at quote time.

Will 3VA1150-3EF32-0JC0 drop into a panel specified around 3VA1010-2ED32-0JC0 without rewiring?

Both are 3-pole SENTRON MCCBs in the same frame family, so the mounting footprint and bus-bar spacing are identical. The 3VA1150-3EF32-0JC0 carries a 50 A TM240 release and 75.6 kA interrupting at 240 V; the 3VA1010-2ED32-0JC0 is a lower-current variant. No rewiring is needed for the same pole count and voltage class, but verify the load current and interrupting requirements against your coordination study before swapping.

What is 3VA1150-3EF32-0JC0's listed depth?

The depth is 70 mm.

What is 3VA1150-3EF32-0JC0's listed width?

The width is 76.2 mm.

MPN
3VA1150-3EF32-0JC0