Skip to main content
Siemens 3VA1150-3EF32-0JH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1150-3EF32-0JH0 SENTRON MCCB, 50 A, 75.6 kA

MPN3VA1150-3EF32-0JH0

Siemens SENTRON 3VA1150-3EF32-0JH0, 3-pole molded case circuit breaker, 50 A rated current at 40 °C, 75.6 kA breaking capacity at 240 V, line protection design, active production.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1150-3EF32-0JH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11503EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1150-3EF32-0JH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C49 A
Current at 60 °C48 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.14.6 W
3VA1150-3EF32-0JH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1150-3EF32-0JH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1150-3EF32-0JH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1150-3EF32-0JH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1150-3EF32-0JH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

It carries a rated current of 50 A at 40 °C, with a breaking capacity of 75.6 kA at 240 V — enough to safely clear high-fault currents in industrial distribution panels without cascading upstream.

The 50 A rating holds steady from 40 °C up to 50 °C, then derates to 49 A at 55 °C and 45 A at 70 °C — a thermal curve that matters if this breaker sits in a warm enclosure or near other heat sources. Breaking capacity drops with voltage: 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at 500 V or 690 V.

The 3VA1150-3EF32-0JH0 measures 130 mm high, 76.2 mm wide, and 70 mm deep — a standard SENTRON MCCB footprint that bolts into a distribution panel or switchboard.

Frequently asked questions

Where can I buy 3VA1150-3EF32-0JH0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA1150-3EF32-0JH0 at 240 V?

The breaking capacity is 75.6 kA at 240 V.

What auxiliary switches does 3VA1150-3EF32-0JH0 include?

It includes 2 auxiliary switches and 1 trip alarm switch (HQ).

MPN
3VA1150-3EF32-0JH0