Skip to main content
Siemens 3VA1150-3EF36-0CC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1150-3EF36-0CC0 SENTRON MCCB, 50 A, 75.6 kA

MPN3VA1150-3EF36-0CC0

Siemens SENTRON 3VA1150-3EF36-0CC0, 3-pole molded case circuit breaker, line protection, 50 A at 40 °C, 75.6 kA interrupting at 240 V, with undervoltage release and 2 auxiliary switches HQ.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1150-3EF36-0CC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11503EF360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1150-3EF36-0CC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C49 A
Current at 60 °C48 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.17.1 W

Protection & Trip Unit

3VA1150-3EF36-0CC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1150-3EF36-0CC0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1150-3EF36-0CC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1150-3EF36-0CC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1150-3EF36-0CC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

50 A MCCB with 75.6 kA interrupting — what the ratings mean for fit

The Siemens 3VA1150-3EF36-0CC0 is a SENTRON molded case circuit breaker (MCCB) rated for line protection in distribution panels. Its 50 A continuous current at 40 °C holds steady through 55 °C (49 A) and derates to 45 A at 70 °C — so the thermal curve matters if your panel runs hot. The 75.6 kA interrupting capacity at 240 V drops to 52.5 kA at 415 V and 32 kA at 440 V, meaning this breaker handles high-fault commercial and light-industrial mains, not just subfeeds. At 690 V it still interrupts 11.9 kA. The 3-pole design suits three-phase loads; the built-in undervoltage release and 2 auxiliary switches HQ are already fitted — no add-on modules needed for status feedback or UV protection.

Panel fit — dimensions and wiring integration

The 3VA1150-3EF36-0CC0 measures 130 mm height, 76.2 mm width, and 70 mm depth — a standard MCCB footprint for DIN-rail or backplate mounting in a distribution board. The 70 mm depth leaves clearance for wiring ducts and gland plates in a typical 200 mm deep enclosure. The 3-pole block accepts copper or aluminum conductors sized for 50 A continuous; the undervoltage release and auxiliary switches are pre-integrated, saving panel space versus add-on kits.

Frequently asked questions

Where can I buy 3VA1150-3EF36-0CC0 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time.

What is the interrupting capacity of 3VA1150-3EF36-0CC0 at different voltages?

At 240 V it interrupts 75.6 kA, at 415 V it interrupts 52.5 kA, at 440 V it interrupts 32 kA, and at 500 V and 690 V it interrupts 11.9 kA.

What is the thermal derating curve for this MCCB?

Rated 50 A continuous at 40 °C through 50 °C (–), it derates to 49 A at 55 °C, 48 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C (–).

What compliance documentation does this brand provide for 3VA1150-3EF36-0CC0?

Siemens provides RoHS, REACH, and IEC/UL certifications for the SENTRON series. The insulation voltage is rated 800 V.

MPN
3VA1150-3EF36-0CC0