Skip to main content
Siemens 3VA1150-3EF36-0DH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1150-3EF36-0DH0 SENTRON MCCB, 50 A, 3-Pole, 75.6

MPN3VA1150-3EF36-0DH0

Siemens SENTRON 3VA1150-3EF36-0DH0, molded case circuit breaker, 3-pole, 50 A rated current, 75.6 kA interrupting capacity at 240 V AC, line protection design, with undervoltage release and auxiliary switches.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1150-3EF36-0DH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11503EF360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1150-3EF36-0DH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C49 A
Current at 60 °C48 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.17.1 W

Protection & Trip Unit

3VA1150-3EF36-0DH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1150-3EF36-0DH0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1150-3EF36-0DH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1150-3EF36-0DH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1150-3EF36-0DH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

What this MCCB carries and where it fits

The Siemens 3VA1150-3EF36-0DH0 is a SENTRON molded case circuit breaker (MCCB) rated 50 A continuous at 40 °C through 50 °C, with a 3-pole construction and line-protection trip curve. It carries a full-load interrupting capacity of 75.6 kA at 240 V AC, 52.5 kA at 415 V, and still holds 11.9 kA at 690 V — enough to handle most industrial fault currents without cascading upstream breakers. An integrated undervoltage release (UVR) and two auxiliary switches plus a trip alarm switch (HQ) come built in, so you don't need to add external accessories for remote status or safety interlock circuits.

Current rating vs. ambient — no derating until 55 °C

This MCCB delivers its full 50 A rating from 40 °C through 50 °C ambient. At 55 °C it drops to 49 A, at 60 °C to 48 A, and at 70 °C to 45 A. That means in a typical 40 °C panel you get the full nameplate without headroom calculations. The rated insulation voltage is 800 V, so it's comfortable in 480 V and 600 V class systems.

Interrupting capacity across voltage levels

The interrupting capacity is specified at five voltage points: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at both 500 V and 690 V. For a 480 V system (common in North American industrial plants) the 32 kA at 440 V is the closest published figure — expect a similar value at 480 V. This gives solid selectivity headroom downstream of a larger feeder breaker.

Built-in auxiliaries and release

The breaker ships with two auxiliary switches and one trip alarm switch (HQ) factory-installed, plus an undervoltage release (UVR). That covers remote status monitoring and safety-related undervoltage trip without separate accessory orders. The UVR is wired to a control voltage — if that voltage drops, the breaker opens, which is standard for emergency-stop or power-loss sequences.

Physical footprint and operating range

Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — a compact 3-pole MCCB footprint that fits standard panel mounting. Operating temperature range is -25 °C to 70 °C, storage from -40 °C to 80 °C. Maximum power loss at rated current is 17.1 W per pole, manageable in a ventilated enclosure.

Frequently asked questions

What is the interrupting capacity of this MCCB at 415 V?

52.5 kA at 415 V AC, with 75.6 kA at 240 V and 11.9 kA at 690 V.

What auxiliary switches and releases come built in?

Two auxiliary switches, one trip alarm switch (HQ), and an undervoltage release (UVR) are factory-installed — no separate accessory order needed.

Where can I buy 3VA1150-3EF36-0DH0 and how is it quoted?

It is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for the latest.

Will 3VA1150-3EF36-0DH0 drop into a panel specified for 3VA1110-5EF32-0AM0 without rewiring?

Both are 3-pole SENTRON MCCBs in the same 3VA family, so the mounting footprint and bus-bar spacing are identical. The 3VA1150-3EF36-0DH0 is a higher-current variant (50 A vs. the 3VA1110's lower rating) with a higher interrupting capacity. Verify the load current and available fault current before substitution — the physical fit is the same, but the electrical ratings differ.

MPN