That makes it a straight line-protection breaker for fixed-load feeders, not a selective-maintenance tool. Undervoltage release (UVR) is built in, so it drops the load if supply voltage falls below the dropout threshold.
Footprint is 76.2 mm wide by 130 mm tall by 70 mm deep — a standard 3-pole MCCB envelope. Current derating is flat from 40 °C to 50 °C at 50 A, then drops to 48 A at 55 °C, 47 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C.