Skip to main content
Siemens 3VA1150-4EF32-0JC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1150-4EF32-0JC0 SENTRON MCCB, 50 A, 3-Pole, 121 k

MPN3VA1150-4EF32-0JC0

Siemens SENTRON 3VA1150-4EF32-0JC0, molded case circuit breaker, 3-pole, 50 A at 40 °C, 121 kA interrupting at 240 V, line protection, shunt trip release.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1150-4EF32-0JC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11504EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1150-4EF32-0JC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C49 A
Current at 60 °C48 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.14.6 W

Protection & Trip Unit

3VA1150-4EF32-0JC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1150-4EF32-0JC0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1150-4EF32-0JC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1150-4EF32-0JC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1150-4EF32-0JC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

What it is and what it does

The Siemens 3VA1150-4EF32-0JC0 is a SENTRON molded case circuit breaker (MCCB) designed for line protection in distribution panels. It carries a continuous current rating of 50 A at 40 °C and holds that rating up through 50 °C, then derates to 49 A at 55 °C, 48 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C — so in a warm enclosure you still get nearly full ampacity. Rated insulation voltage is 800 V, and the interrupting capacity varies by line voltage: 121 kA at 240 VAC, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V. That gives you solid SCCR headroom for most industrial service-entrance or feeder applications. The 3-pole unit ships with a factory-installed shunt trip (STL) auxiliary release and two HQ auxiliary switches. No undervoltage release, no ground-fault monitoring, no communication module — it's a straightforward thermal-magnetic MCCB with a remote trip coil for emergency-off or safety circuits.

Panel fit and integration

The breaker measures 130 mm high, 76.2 mm wide, and 70 mm deep — a standard SENTRON 3VA footprint. The 70 mm depth (2.76 in) leaves clearance behind a typical enclosure door. Maximum power dissipation is 14.6 W at rated load, so in a multi-breaker lineup you need to account for the cumulative heat. The operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C.

Frequently asked questions

What auxiliary options are factory-installed on this MCCB?

It ships with a shunt trip (STL) release and two HQ auxiliary switches. No undervoltage release, ground-fault monitoring, or communication module.

MPN
3VA1150-4EF32-0JC0