Skip to main content
Siemens 3VA1150-4EF32-0KA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1150-4EF32-0KA0 SENTRON MCCB, 50 A, 121 kA at 240

MPN3VA1150-4EF32-0KA0

Siemens SENTRON 3VA1150-4EF32-0KA0 molded case circuit breaker, 3-pole, line protection, 50 A rated continuous current, breaking capacity 121 kA at 240 V, with shunt trip release.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1150-4EF32-0KA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1150-4EF32-0KA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C48 A
Current at 60 °C47 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA
3VA1150-4EF32-0KA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1150-4EF32-0KA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1150-4EF32-0KA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1150-4EF32-0KA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1150-4EF32-0KA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1150-4EF32-0KA0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying a rated continuous current Iu of 50 A across the ambient range up to 50 °C, with a slight thermal derating at higher temperatures: 48 A at 55 °C, 47 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C. Breaking capacity is specified at multiple common voltages: 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V. For a 400 V three-phase industrial supply the 75.6 kA figure provides substantial fault-current headroom, and the 121 kA at 240 V covers high-fault single-phase taps. Dimensions are 76.2 mm wide, 130 mm high, and 70 mm deep — a compact footprint for a 50 A MCCB, fitting standard SENTRON panel cutouts.

This part is in active current production per the manufacturer's lifecycle stage designation.

Mounts on DIN rail or panel baseplate via SENTRON snap-on. Depth is 70 mm. No auxiliary contacts or communication modules included.

MPN
3VA1150-4EF32-0KA0