Skip to main content
Siemens 3VA1150-4EF36-0AE0 — Molded Case Circuit Breakers (MCCB)

SENTRON 3VA1150-4EF36-0AE0 MCCB, 50 A, 121 kA at 240 V

MPN3VA1150-4EF36-0AE0

Siemens SENTRON 3VA1150-4EF36-0AE0 molded case circuit breaker, 3-pole, 50 A rated current, TM240 thermal-magnetic release, 121 kA breaking capacity at 240 V AC, line protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1150-4EF36-0AE0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11504EF360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1150-4EF36-0AE0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C49 A
Current at 60 °C48 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.14.6 W
3VA1150-4EF36-0AE0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1150-4EF36-0AE0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1150-4EF36-0AE0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4
3VA1150-4EF36-0AE0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1150-4EF36-0AE0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The SENTRON 3VA1150-4EF36-0AE0 is a 3-pole molded case circuit breaker rated for 50 A continuous current at 40 °C ambient, with a TM240 thermal-magnetic trip unit. That 50 A holds flat through 50 °C, then derates to 49 A at 55 °C, 48 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C — so if the panel runs hot, you still have headroom down to 45 A before the breaker nuisance-trips. The breaking capacity is 121 kA at 240 V AC, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V. That 121 kA at 240 V tells you it can interrupt a bolted fault on a large transformer secondary without welding its contacts shut — the kind of fault current you see on a 1500 kVA pad-mount feeding a 480/277 V panel. The TM240 release means the thermal element tracks overloads on a 50 A frame, while the magnetic instantaneous trips at roughly 10× the rated current — so 500 A or so. That's a standard motor-starting profile, but verify your inrush against the magnetic pickup curve if you're feeding a high-efficiency motor with locked-rotor current near 8× FLA. It's a straight thermal-magnetic breaker for feeder or branch protection. The 14.6 W maximum power loss matters for panel thermal calculations: if you pack six of these in a row, that's nearly 90 W of heat inside the enclosure that the ventilation has to clear.

The 3VA1150-4EF36-0AE0 measures 70 mm deep, 76.2 mm wide, and 130 mm tall. That 76.2 mm width is exactly 3 inches — standard for a 3-pole 50 A frame MCCB in a Siemens panelboard or a separate enclosure. Mounting is via the standard 3VA screw-clamp or plug-in base; no DIN-rail adapter for this frame size — it bolts to the panel or clips into the SENTRON distribution block.

The 3VA1110-5ED36-0AC0 is a 3-pole 100 A frame with an electronic ETU release, compared to this 50 A thermal-magnetic TM240. The 3VA1110 is physically larger — 90 mm wide versus 76.2 mm — so it will not drop into the same panel cutout or bus-bar spacing without re-drilling the mounting holes. The breaking capacities also differ: the 100 A frame typically carries lower interrupting ratings at the same voltage because the higher continuous rating stresses the arc chamber. If your BOM calls for a 50 A line-protection breaker, the 3VA1150-4EF36-0AE0 is the correct fit; the 3VA1110-5ED36-0AC0 would require re-wiring the bus and re-coordinating the downstream devices.

Frequently asked questions

Where can I buy 3VA1150-4EF36-0AE0 and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead-time estimate.

Will 3VA1150-4EF36-0AE0 drop into a panel specified around 3VA1110-5ED36-0AC0 without rewiring?

No — the 3VA1150 is 76.2 mm wide versus the 3VA1110's 90 mm frame, so the mounting holes and bus-bar spacing differ. A direct swap would require re-drilling the panel and re-terminating the bus connections.

What is the breaking capacity of 3VA1150-4EF36-0AE0 at 415 V?

The breaking capacity is 75.6 kA at 415 V AC, which is typical for a 50 A frame MCCB on a 400 V industrial distribution system with a large transformer.

MPN
3VA1150-4EF36-0AE0