Skip to main content
Siemens 3VA1150-5EF32-0HA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1150-5EF32-0HA0 SENTRON MCCB, 50 A, 3-Pole, 187 k

MPN3VA1150-5EF32-0HA0

Siemens SENTRON 3VA1150-5EF32-0HA0, 3-pole molded case circuit breaker, 50 A at 40 °C, TM240 thermal-magnetic release, 187 kA breaking capacity at 240 V, shunt trip (STL).

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1150-5EF32-0HA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11505EF320AA0
3VA1150-5EF32-0HA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C49 A
Current at 60 °C48 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.14.6 W
3VA1150-5EF32-0HA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1150-5EF32-0HA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1150-5EF32-0HA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1150-5EF32-0HA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1150-5EF32-0HA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Siemens 3VA1150-5EF32-0HA0 — 50 A MCCB with TM240 Release and Shunt Trip

It carries a continuous current rating of 50 A at 40 °C, with minimal thermal derating up to 70 °C (45 A at 70 °C). The TM240 thermal-magnetic release provides fixed overload and short-circuit protection curves, while the integrated shunt trip (STL) allows remote tripping for emergency-off or supervisory control circuits. Breaking capacity is the headline number here: 187 kA at 240 V AC, stepping down to 121 kA at 415 V and 75.6 kA at 440 V. That SCCR headroom means this breaker can sit upstream of a high-fault panel without cascading — useful for industrial switchboards where the transformer rating drives available fault current above 100 kA.

The shunt trip (STL) auxiliary release requires a separate control voltage — verify polarity and free-wheel diode on the coil before energizing. Maximum power loss is 14.6 W, so ventilation in a sealed enclosure is advisable if multiple breakers are ganged.

Frequently asked questions

Does 3VA1150-5EF32-0HA0 include a shunt trip?

Yes, it includes a shunt trip (STL) auxiliary release for remote tripping, designed for emergency-off or supervisory control circuits.

MPN
3VA1150-5EF32-0HA0