It's rated 50 A continuous at 40 °C and holds that rating up to 50 °C ambient — above that it derates to 49 A at 55 °C and 45 A at 70 °C, so if your panel runs hot you need to account for the thermal curve. Breaking capacity scales with system voltage: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 500 V or 690 V.
The trip indicator and voltage trigger are both present, so you get visual and electrical status feedback for the control system.