Skip to main content
Siemens 3VA1150-5EF36-0BA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1150-5EF36-0BA0 SENTRON MCCB, 50 A, 3-Pole, TM240

MPN3VA1150-5EF36-0BA0

Siemens SENTRON 3VA1150-5EF36-0BA0, molded case circuit breaker, 3-pole, 50 A, TM240 thermal-magnetic release, line protection, 187 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1150-5EF36-0BA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1150-5EF36-0BA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C48 A
Current at 60 °C47 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 690 V17 kA

Protection & Trip Unit

3VA1150-5EF36-0BA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1150-5EF36-0BA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1150-5EF36-0BA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1150-5EF36-0BA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1150-5EF36-0BA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

What this MCCB is and what it does

The Siemens SENTRON 3VA1150-5EF36-0BA0 is a 3-pole molded case circuit breaker (MCCB) rated for 50 A continuous current, built for line protection in distribution panels and motor branch circuits. It carries a TM240 thermal-magnetic overcurrent release — the thermal element handles overloads, the magnetic element clears short circuits — and includes an integrated undervoltage release (UVR) that trips the breaker when control voltage drops below the dropout threshold.

Breaking capacity — what the ratings mean for your fault-current study

This MCCB is rated to interrupt 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V. Those are the maximum fault currents the breaker can safely clear at each voltage level without welding contacts or rupturing the case.

Continuous current and thermal derating

The breaker carries its full 50 A rating from 40 °C through 50 °C ambient. Above that it derates: 48 A at 55 °C, 47 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C.

Physical fit and panel integration

The 3VA1150-5EF36-0BA0 measures 130 mm high, 76.2 mm wide, and 70 mm deep. The front face carries an IP40 protection rating — fine for a clean indoor panel, but not for washdown areas. It mounts on a DIN rail or directly to a backplate via the screw terminals. The 3-pole footprint is standard for this class; plan for a 76.2 mm-wide slot in your panel layout.

Frequently asked questions

Will 3VA1150-5EF36-0BA0 drop into a panel that was specified around 3VA1112-5EF32-0CA0 without rewiring?

Both are 3-pole SENTRON MCCBs with the same mounting footprint and terminal layout, so mechanical fit is identical. The difference is in the release and rating — this one uses a TM240 release at 50 A, while the 3VA1112-5EF32-0CA0 uses a different release and current rating. Check the load side before swapping.

MPN
3VA1150-5EF36-0BA0