The 3VA1150-6EF32-0AA0: Interrupting capacity is the headline: 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at both 500 V and 690 V. That 220 kA figure at 240 V means it handles high-fault utility feeds without cascading upstream — useful for main breaker positions in industrial switchboards. At 690 V the 17 kA still covers most motor-drive branch circuits. Three-pole, rated insulation voltage 800 V, front IP40 protection. Dimensions are 70 mm deep, 76.2 mm wide, 130 mm tall — fits standard MCCB mounting footprints in Siemens SENTRON panels or third-party enclosures with the same cutout. Max power loss 14.6 W, so ventilation in a sealed enclosure is worth checking if you pack multiple breakers.

Siemens 3VA1150-6EF32-0AA0 SENTRON MCCB, 50 A, 3-Pole, 220 k
MPN3VA1150-6EF32-0AA0
Active
Siemens SENTRON 3VA1150-6EF32-0AA0, 3-pole molded case circuit breaker, 50 A rated current, TM240 thermal-magnetic release, interrupting capacity 220 kA at 240 V AC.
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026
Specifications
Identification
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
Ratings
| Parameter | Value |
|---|---|
| Number of poles | 3 |
| Rated operational voltage Ue (AC) | 690 V |
| Rated insulation voltage Ui | 800 V |
| Current at 40 °C | 50 A |
| Current at 45 °C | 50 A |
| Current at 50 °C | 50 A |
| Current at 55 °C | 49 A |
| Current at 60 °C | 48 A |
| Current at 65 °C | 46 A |
| Current at 70 °C | 45 A |
| Switching capacity class | H |
| Breaking capacity at 240 V | 220 kA |
| Breaking capacity at 415 V | 154 kA |
| Breaking capacity at 440 V | 121 kA |
| Breaking capacity at 500 V | 17 kA |
| Breaking capacity at 690 V | 17 kA |
| Power loss, max. | 14.6 W |
Protection & Trip Unit
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | TM240 |
| Overcurrent protection function | LI |
| Ground-fault monitoring | Without |
| Grounding protection function | No |
Construction & Connection
| Parameter | Value |
|---|---|
| Main circuit connection type | nut keeper kit on both ends |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
Accessories & Functions
| Parameter | Value |
|---|---|
| Undervoltage release | No |
| Voltage trigger | No |
| Trip indicator | No |
| Communication function | No |
| Measurement function | No |
| Motor drive option | Yes |
| Auxiliary CO contacts | 0 |
Environmental
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
Mechanical
| Parameter | Value |
|---|---|
| Mechanical service life (operating cycles), typ. | 20 000 |
| Height | 130 mm |
| Width | 76.2 mm |
| Depth | 70 mm |
| Height (in) | 5.12 in |
| Width (in) | 3 in |
| Depth (in) | 2.76 in |
Product details
Frequently asked questions
What is the interrupting capacity of this MCCB at 240 V?
220 kA at 240 V AC, dropping to 154 kA at 415 V and 121 kA at 440 V.
What overcurrent release does the 3VA1150-6EF32-0AA0 use?
It uses a TM240 thermal-magnetic release — no separate trip unit module required.
What are the mounting dimensions for this breaker?
70 mm deep, 76.2 mm wide, 130 mm tall — standard 3-pole MCCB envelope.
Where can I buy the 3VA1150-6EF32-0AA0 and get current pricing?
Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.
MPN
3VA1150-6EF32-0AA0