Siemens 3VA1150-6EF32-0AE0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1150-6EF32-0AE0 SENTRON MCCB, 50 A, 220 kA at 240

MPN3VA1150-6EF32-0AE0

Siemens SENTRON 3VA1150-6EF32-0AE0, 3-pole molded case circuit breaker, 50 A continuous at 40 °C, TM240 thermal-magnetic release, 220 kA interrupting capacity at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1150-6EF32-0AE0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11506EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1150-6EF32-0AE0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C49 A
Current at 60 °C48 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.14.6 W

Protection & Trip Unit

3VA1150-6EF32-0AE0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1150-6EF32-0AE0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1150-6EF32-0AE0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA1150-6EF32-0AE0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1150-6EF32-0AE0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

What this MCCB brings to the panel

The Siemens 3VA1150-6EF32-0AE0 is a 3-pole SENTRON molded case circuit breaker (MCCB) rated for 50 A continuous at 40 °C, with the TM240 thermal-magnetic release handling the overload and short-circuit protection. The 220 kA interrupting capacity at 240 V means this breaker can safely clear a fault up to that level without upstream coordination issues — important for high-fault panels near large transformers or service entrances. At 415 V it still interrupts 154 kA, dropping to 121 kA at 440 V, and 17 kA at 500 V and 690 V respectively, giving you selectivity headroom across common industrial voltages.

Thermal derating and real-world loading

The 50 A rating holds flat from 40 °C through 50 °C — no derating needed in a typical ventilated enclosure. At 55 °C it drops to 49 A, then 48 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C. If your panel runs hot near other heat sources, you still get 45 A at the upper operating limit. The max power loss is 14.6 W, manageable for a DIN-rail enclosure without forced cooling.

Integration notes for the panel builder

The breaker measures 76.2 mm wide, 130 mm tall, and 70 mm deep — a standard footprint that fits most DIN-rail or panel-mount MCCB arrangements. The 3-pole design with 4 auxiliary switches (HQ type) gives you plenty of status feedback for PLC or HMI inputs. No undervoltage release, no ground-fault monitoring, no communication module on this variant — it's a straight line-protection device. Insulation voltage rated at 800 V, operating range from -25 °C to 70 °C, storage from -40 °C to 80 °C.

Frequently asked questions

How do I get pricing and availability for 3VA1150-6EF32-0AE0?

Pricing and availability are confirmed at quote time against an RFQ through our independent distribution channel. Submit a request with your quantity and delivery timeline, and we'll return current market pricing and lead time.

What is the interrupting capacity of this MCCB at different voltages?

At 240 V it interrupts 220 kA, at 415 V it's 154 kA, at 440 V it's 121 kA, and at 500 V and 690 V it's 17 kA. This covers most industrial service-entrance and distribution panel fault levels.

Does this breaker have a thermal-magnetic or electronic trip unit?

It uses a TM240 thermal-magnetic overcurrent release — fixed thermal and magnetic trip settings, no electronic adjustment. That keeps it simple for standard feeder and branch circuit protection.

MPN