It's a 3-pole unit rated 50 A at 40 °C, with a rated insulation voltage of 800 V — so it handles standard 400/480 VAC buswork with margin.
Breaking capacity — the real number for fault duty
At 240 VAC this breaker interrupts 220 kA; at 415 VAC it's 154 kA, and at 440 VAC it's 121 kA.
Thermal derating — don't oversize the frame
Above that it derates: 49 A at 55 °C, 48 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C.