Specifications

3VA1150-6EF36-0AE0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11506EF360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1150-6EF36-0AE0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C49 A
Current at 60 °C48 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.14.6 W
3VA1150-6EF36-0AE0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1150-6EF36-0AE0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1150-6EF36-0AE0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4
3VA1150-6EF36-0AE0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1150-6EF36-0AE0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

It carries a 50 A continuous rating across ambient temperatures from 40 °C to 50 °C, derating to 45 A at 70 °C — a thermal curve you need to check against your enclosure's internal temperature rise, especially in a packed panel. Breaking capacity is the headline spec here: 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 500 V and 690 V. That 220 kA figure at 240 V gives you serious fault-current headroom for high-capacity transformer secondaries or large motor-control-center feeds. The 17 kA at 690 V still covers most industrial 690 V distribution. That makes it a straightforward choice for standard feeder protection where you don't need the selectivity flexibility of an electronic trip unit.

The 3VA1150-6EF36-0AE0 measures 130 mm high, 76.2 mm wide, and 70 mm deep — a 3-pole frame that fits standard Siemens SENTRON mounting accessories and busbar systems. The 70 mm depth means it projects less than many competing MCCBs, which helps when you're routing cables behind a backplate.

The 3VA1150-6EF36-0AE0 is a current-production SENTRON MCCB.

Frequently asked questions

What type of overcurrent release does 3VA1150-6EF36-0AE0 use?

It uses a TM240 thermal-magnetic overcurrent release — fixed thermal and magnetic trip settings, no electronic adjustment.